A-3
Sensitivities and corresponding levels are shown in Table A-2 for TrueAlarm
types.
Table A-2. TrueAlarm Levels and Sensitivities
Levels Sensitivities
PHOTOs XPHOTOs IONs HEATs
Level 1
0.5% 0.2% 0.5%
117°F (X°C)
Level 2
1.0% 0.5% 0.9%
135°F (57°C)
Level 3
1.5% 1.0% 1.3%
155°F (68°C)
Level 4
2.0% 1.5% 1.7%
155°F (68°C)
Level 5
2.5% 2.0% 1.7%
155°F (68°C)
Level 6
3.0% 2.5% 1.7%
155°F (68°C)
Level 7
3.7% 3.7% 1.7%
155°F (68°C)
Table A-3 lists the Monitor Hardware Device Types for the 4010.
Table A-3. Monitor Hardware Device Types
Device Type Description
MAZAM Class A Monitor ZAM (T-sense)
MBZAM Class B Monitor ZAM (T-sense)
ADRPUL Addressable Pull Station
SIAM Supervised IAM (T-sense)
CANPUL Canadian 2-stage Pull Station
KACPUL International KAC Pull Station
Continued on next page
Hardware Device Types, Continued
TrueAlarm Levels and
Sensitivities
Monitor Hardware Device
Types
Device/Point T
y
pes
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
BrandSimplex
Model4010
CategoryFire Alarms
LanguageEnglish

Related product manuals