There is a risk of bodily injury and material damage if the parameterized
software limit switches P300 and P301 are exceeded!
The parameterized software limit switches P300 and P301, which relate to the
actual value of position, are inoperative in “speed control” mode.
Range overruns can occur in rotary applications, for example, due to the
integrated position measuring system. Depending on the direction of rotation,
this is manifested by a skip of the actual value of position (P100):
Max --> Min / Min --> Max.
The application must therefore not be dependent on the actual value of position!
Inhibit ramp function
generator
Drive decelerates at current limit, converter remains
energized.
Enable ramp function
generator
Stop ramp function
generator
Drive decelerates on the configured deceleration ramp
(P203).
Drive runs up on the configured acceleration ramp (P202)
until the speed setpoint (P201) is reached.
Drive decelerates on the configured deceleration ramp
(P203) until it stops.
Table 13: Control word, speed control
Not supported by the encoTRive. Tracking error monitoring is active instead!
The preselected speed (P201) has been reached.
Actual speed less than
set speed
The preselected speed (P201) has not yet been reached.
Table 14: Status word, speed control