Limit switch input positive
Limit switch input negative
Release of the integrated brake
Table 28: Overview of the Limit switch function
The activation of the hardware limit switch functions must be executed first, after
this the controller can be switched active.
Example:
On the digital inputs 0 and 1 two hardware limit switches, as normally closed contacts, are connected.
To activate the corresponding function, the following value must be transferred for parameter P807:
Input 0 as positive limit switch, low-active --> Byte 0 = 03
Input 1 as negative limit switch, low-active --> Byte 1 = 05
Parameter P807 = 0x0000 0503 = 1283 dec.
9.2.2 Outputs
About this 4-byte parameter P808 “Digital OUT Function”, to the 4 digital outputs different functions
can be assigned. For each output one byte is reserved.