PROFINET communication with encoTRive
TR-Electronic GmbH 2008, All Rights Reserved Printed in the Federal Republic of Germany
Page 162 of 252 TR - EMO - BA - DGB - 0019 - 08 06/06/2019
5.4.1.2 Write command: Write P915 with a number of values
The control wants to write parameter 915 "PZD configuration, setpoints" with the
following values:
P915[1] = 200 (target position), P915[2] = 201 (speed),
P915[3] = 202 (acceleration), P915[4] = 203 (deceleration)
Request IO controller => encoTRive
Request ID (write parameter)
Axis (content not relevant)
Number of parameters (always 1)
Attribute (access to value)
First subindex (High Byte)
First subindex (Low Byte)
Response encoTRive => IO controller:
a) If executed successfully:
Request reference (mirrored from request)
Response ID (parameter written successfully)
Axis (mirrored from request)
Number of parameters (mirrored from request)
b) In the event of failure:
The error number is assumed to be 0xABCD
Request reference (mirrored from request)
Response ID (error when writing parameter)
Axis (mirrored from request)
Number of parameters (mirrored from request)