8.5.2.5 PNU 927, Control priority
This parameter defines who may have access to parameters.
In addition to PROFINET, encoTRive supports access to parameters of the OD via serial interface.
If access occurs via the serial interface, parameter access via PROFINET is locked.
Value 1: Control priority local, i.e. via serial interface
Value 2: Control priority PROFINET-IO
8.5.2.6 PNU 928, PZD control priority
Defines who can have write access to the process data. It is possible that parameters of the OD may
be accessed simultaneously via the cyclic RT data and via the record data.
Value 1: RT data have PZD control priority. Record data write access to PZD parameters is refused.
Value 2: Record data have PZD control priority. IO data are ignored.
8.5.2.7 PNU 930, Operating mode
Selection of operating mode.
8.5.2.8 PNU 947, Error/Faults
Fault memory. Fault messages are stored permanently in a ring buffer. If a new fault is present, then
this is indicated by ZSW.3=1 (“Fault present”)
8.5.2.9 PNU 953, Warning
Indicates whether a fault is present.