2.1
Model System Startup Procedure
2-5
4.
Press the Key on the Digital Operator to display the Auxiliary Function Mode
main menu, and use the Keys to select Fn005.
5.
Press the Key to switch to the Fn005 parameter initialization execution
display.
* If the display does not change and “NO-OP” is displayed on the status display, a Write
Prohibited password has been set using Fn010 and the user settings cannot be initialized.
Clear the write protection and execute the operation again.
6.
Press the Key again and execute Fn005.
“Parameter Init” will flash during initialization.
The flashing will stop when initialization has been completed and the status display will
change from BB to Done to A.941.
To cancel initialization, press the Key before pressing the Key. The display
returns to the Auxiliary Function Mode main menu.
7.
Turn the SERVOPACK control and main power supplies from OFF to ON to enable the
initialization.
2.1.4 MP2300 Self-configuration
Execute self-configuration to automatically configure the Optional Modules mounted to the Basic
Module and the devices connected to the MECHATROLINK.
This section explains the method for self-configuration.
1.
Check that the power supply of the
Σ
-
III
SERVOPACK is ON.
2.
Turn OFF the 24-VDC power supply to the MP2300.