Menu 7 Introduction Parameter x.00
Parameter
description format
Keypad and
display
CT Modbus
RTU
User
programming
CT Soft Menu 0
Advanced parameter
descriptions
80 Commander SK Advanced User Guide
www.controltechniques.com Issue Number: 2
9.8 Menu 7: Analog inputs and outputs
Table 9-9 Menu 7 parameters: single line descriptions
Parameter Range Default Setting Update Rate
7.01 Analog input 1 monitor (terminal T2) 0.0 to 100.0%
5 ms
7.02 Analog input 2 monitor (terminal T4) 0.0 to 100.0%
5 ms
7.03 Not used
7.04 Heatsink temperature -128 to 127 °C B
7.05 Not used
7.06 Analog input 1 mode (terminal T2) {16} 0 to 6 4 B
7.07 Not used
7.08 Analog input 1 scaling 0.000 to 4.000 1.000 B
7.09 Analog input 1 invert 0 or 1 0 5 ms
7.10 Analog input 1 destination Pr 1.01 to Pr 21.51 Pr 1.36 Drive reset
7.11 Analog input 2 mode (terminal T4) 0 or 1 0 B
7.12 Analog input 2 scaling 0.000 to 4.000 1.000 B
7.13 Analog input 2 invert 0 or 1 0 5 ms
7.14 Analog input 2 destination Pr 1.01 to Pr 21.51 Pr 1.37 Drive reset
7.15 Not used
7.16 Not used
7.17 Not used
7.18 Not used
7.19 DAC output source Pr 0.01 to Pr 21.51 Pr 2.01 Drive reset
7.20 DAC output scaling 0.000 to 4.000 1.000 21 ms
7.21 Not used
7.22 Not used
7.23 Not used
7.24 Not used
7.25 Not used
7.26 Not used
7.27 Not used
7.28 Current loop loss indicator 0 or 1 5 ms
7.29 Not used
7.30 Analog input 1 offset ±100.0% 5 ms
7.31 Analog input 2 offset
±100.0% 5 ms
7.32 Not used
7.33 Analog output control (Terminal B1) {36} 0 to 4 0 Drive reset
7.34 IGBT junction temperature
±200 °C B
7.35 Drive thermal protection accumulator 0 to 100%
B