146 of 165 M-SV-VT-001-EN Rev. A
Installation (Revisions A and B):
1. Place the DC-DC in the panel and secure in place.
2. Connect the HV DC input cable to J1; 24 VDC output cable to J4; and 250 VDC output cable to J2.
3. Connect the grounding wires to M4, M5, J6, and J7.
4. Close the panel.
5. Restore power to the VFD.
4. Remove the securing hardware holding the DC-DC frame to the panel.
5. Remove the DC-DC from the panel.
OEM Module Components
Figure 189 - DC-DC J2 and
4 Connections
J4 Connector
J2 Connector
Installation (Revisions C and Later):
1. Place the DC-DC in panel and secure in place.
2. Connect the HV DC input cable to J1; 24 VDC output cable to J4; and 250 VDC output cable to J2.
3. Close the panel.
4. Restore power to the VFD.