Compressor Components
11. Once the valve has cooled back down, reinstall the electronic power head and retaining clip if
removed.
Figure 38 - Brazing the EXV
3.2.7.4 Torque
Specications
Description Nm Ft.Lb. In.Lb.
Flange, SHCS, M14x40 (Revision A) 70 52 620
Flange, SHCS, M8x25 (Revisions B and later) 30 22 266
Table 11 - EXV Torque
Specications
3.2.8 EXV Cable The EXV Cable connects the CCM to the EXV.