34 of 165 M-SV-VT-001-EN Rev. A
Compressor Components
3.2.2.3 Calibration
1. Connect to the Compressor with the SMT.
2. Open the Valve Control Setup Tool.
3. Under the IFV tab, click on Calibrate IFV.
NOTE
IFV calibration may take up to several minutes.
4. A pop-up window in the SMT should state that the IFV calibrated successfully.
10. Press the Up Arrow button until you reach Parameter 26.
11. Press the Enter/Edit button.
12. Press the Up Arrow button to select 5.
13. Press the Enter/Edit button.
14. Hold the Enter/Edit button for 2 seconds to exit the programming mode.
3.2.3 ICM Body The ICM attaches to the IFV Pipe Assembly. The driving force from the IFV is transferred via a magnetic
coupling through the stainless steel valve stem on the Bonnet/Function Module. This action permits
the regulation of the refrigerant ow to the inlet of the rst stage diuser.
ICM Body Bolts - 100
Nm (74 ft.lb.) (4 places)
ICM Adapter/Valve
Stem
Bonnet/Function
Module
Figure 21 - ICM Body
3.2.2.4 Torque
Specications
Description Nm Ft.Lb. In.Lb.
IFV Set Screws 3 - 27
Table 7 - IFV Actuator Torque
Specications