90 of 165 M-SV-VT-001-EN Rev. A
3.7.1.9 Motor
Temperature Sensor
Cable
Figure 103 - Motor
Temperature Sensor Cable
The motor temp sensor cable connects the motor temperature sensor to the CCM.
3.7.1.9.1 Removal and
Installation
Removal:
1. Isolate the Compressor power as described in the “Electrical Isolation of the Compressor/VFD”
section of this manual.
2. Remove the Service Side Cover.
3. Locate and remove the connector from MOT RTD (J12) located on the top-left corner of the CCM
Board.
5
6
7
4
8
3
9
2 1
10
11
Compressor Components
Figure 102 - Feed Through
Connector