66 of 165 M-SV-VT-001-EN Rev. A
Compressor Components
Temperature
º C
Resistance
Ω
Temperature
º C
Resistance
Ω
Temperature
º C
Resistance
Ω
-50 803.1 40 1155.4 130 1498.3
-40 842.7 50 1194.0 140 1535.8
-30 882.2 60 1232.4 150 1573.3
-20 921.6 70 1270.8 160 1610.5
-10 960.9 80 1309.0 170 1647.7
0 1000.0 90 1347.1 180 1684.8
10 1039.0 100 1385.1 190 1721.7
20 1077.9 110 1422.9 200 1758.6
30 1116.7 120 1460.7
Table 20 - Stator
Thermistor R/T Curve
9. Verify resistance of each circuit at the external connector to housing (ground).
• Should be “open.”
10. If the Stator Temperature Sensor Feed Through is suspected to have a problem, remove it and
test as above directly at the internal connector. Refer to the “Stator Temperature Sensor Feed
Through” section of this manual.
11. Restore power to the Compressor.
NOTE
Measured values must be within ± 10% of the values in Table 20 (Stator Thermistor R/T Curve).