5:Zero-speed running(no output at stop)
If the AC drive runs with the output frequency of 0, the terminal becomes ON. If the AC drive
is in the stop state, the terminal becomes OFF.
6:Motor overload pre-warning
The AC drive judges whether the motor load exceeds the overload pre-warning threshold
before performing the protection action. If the pre-warning threshold is exceeded, the
terminal becomes ON. For motor overload parameters, see the descriptions of PA.00 to
PA.02.
7:AC drive overload pre-warning
The terminal becomes ON 10s before the AC drive overload protection action is performed.
8:Set count value reached:The terminal becomes ON when the count value reaches the
value set in PE.08.
9:Designated count value reached:The terminal becomes ON when the designated value
reaches the value set in PE.09.
10:Length reached:The terminal becomes ON when the detected actual length exceeds
the value set in PE.05.
11:PLC cycle complete:When simple PLC completes one cycle, the terminal outputs a
pulse signal with width of 250 ms.
12:Current running time reached:If the current running time of the AC drive exceeds the
time set in P2.51, the terminal becomes ON.
13:Frequency limited
If the set frequency exceeds the frequency upper limit or lower limit and the output