9
Caution
Since all adjustable frequency AC drives from
our company has been subjected to hi-pot test
before delivery, users are prohibited from
implementing such a test on this equipment.
Failure to comply may result in equipment
damage.
Signal wires should to the best of the possibility
be away from main power lines. If this cannot be
ensured, vertical cross-arrangement shall be
implemented, otherwise interference noise to
control signal may occur.
If motor cables are longer than 100m, it is
recommended output AC reactor be used. Failure
to comply may result in faults.
Before Power-
on
Danger
Inverter shall be power-on only after the front
cover is assembled. Risk of electrical hazard.
Caution
Verify that the input voltage is identical to the
rated voltage of product, correct wiring of input
terminals R, S, T and output terminals U, V, and
W, wiring of inverter and its peripheral circuits,
and all wires should be in good connection. Risk
of inverter damage.