AH500 Module Manual
16-2
16.1 Introduction to AHRTU-ETHN-5A
Thank you for choosing Delta AHRTU-ETHN-5A module. Please read the product instruction
carefully before use so as to install and operate the product properly.
AHRTU-ETHN-5A is AH series remote I/O module. AH series CPU such as AHCPU5x1-EN of V2.0
and above can easily control AH digital I/O module and analog I/O module through EtherNet/IP
communication protocol.
16.1.1 Function
Supports the standard EtherNet/IP communication protocol slave, I/O connection through
cyclic data exchange as well as explicit message connection through acyclic data exchange.
Provides module status (MS), network status (NS), I/O module status and a seven-segment
display showing AHRTU-ETHN-5A’s status and error code.
Provides AHRTU error processing mechanism by setting how to process I/O modules and
AHCPU when an error occurs in I/O modules.
Able to connect 1 main backplane and 7 extension backplanes. Max. 68 AH series I/O
modules are connectable to AHRTU-ETHN-5A. Max. number of input and output points and
max. number of channels are 3744 and 544 respectively.
16.1.2 Specification
Ethernet
protocol
EtherNet/IP, MODBUS TCP
10/100 Mbps Auto-Detection
interface
RJ-45 with Auto MDI/MDIX
ports
2 (X1, X2)
MODBUS TCP
General
Server
TCP connections
32
EtherNet/IP
General
CIP service type_ IO
Connection
connections
96
connections
48 (Servers)