Issue 4.5 Aug 2005 IntelliBell 14-7
Strobe Operation - The Strobe Output switches on and switches off the Strobe. By default, the IB option Strobe
Follows Sounder is cleared. When the Strobe Follows Sounder option is set by the operator, the Strobe is controlled
only by the Sounder Output.
Self Test Output (TE) - This output function controls the unit’s self test operation. By default, it is set to 0 and therefore
disabled. When the TE output is set and triggered by the panel, the unit will execute three consecutive tests. The
sounder, strobe, and battery circuits are tested and if nothing is reported to the panel within 30 seconds, the engineer
may conclude that the three circuits have passed their tests.
Program Enable Output (PEA) - A program enable output must be programmed for this feature to be used. When this
output is turned on, the IB will be fully disabled. Typically, this output would be used to allow the installation engineer
to attend to the IB after an alarm.
This output must be switched off for the IB to return to normal operation.
Reset Memory (RS) - The IB memory may be reset by selecting this menu option and following the flow chart. The
process of resetting memory is made difficult to erroneously select by requiring the engineer to press all three
programming keys simultaneously twice in succession.