Installation
d) In case that upper side obstacles exist (serial units) e) In case of front side and either of the sides are open (serial units)
200
300
0 < L ≤ 1/2 H A 500
1/2 H < L ≤ H A 1000
≤ 300
f) In case that surrounding wall exist (serial units)
A
L
1000
g) Horizontal (multiple units) h) Vertical (multiple units)
0 < L ≤ 1/2 H A ≥ 100
1/2 H < L ≤ H A ≥ 200
≥ 1000
≥ 400
≥ 2000
≥ 250
400
250
250
400
250
≥ 250
Do not stack more than two units in height. - Close gap (*) to avoid recirculating discharge air flow.
a) In case of front side and either of the sides are open (single unit) b) In case that surrounding wall exist (single unit)
100
500
1000
500
50
c) In case that upper side obstacles exist (single unit)
50
100
300
50
300
100
0 < L ≤ 1/2 H A 500
1/2 H < L ≤ H A 1000
0 < L ≤ 1/2 H A 200
1/2 H < L ≤ H A 350
0 < L ≤ 1/2 H A 500
1/2 H < L ≤ H A 1000

foundation height.
Do not stack more than two units in height.
