9
General data
2.2 ERP performance data for space heating
This appliance must be installed, maintained and dismantled by professionals. Do not pour contained refrigerant
into the atmosphere since this refrigerant uid is a uorinated greenhouse gas regulated under European Regulation
(EU)Nº 517/2014. ERP performance data is tested in accordance with the standard EN14825.
2.2.1 ERP data - Hi-Therma Split
For space heating
Model
44(2.0 HP) 60(2.5 HP) 80(3.0 HP)
Outdoor unit AHW-044HCDS1 AHW-060HCDS1 AHW-080HCDS1
Indoor unit AHM-044HCDSAA AHM-060HCDSAA AHM-080HCDSAA
Water outlet temperature 35°C 55°C 35°C 55°C 35°C 55°C
Product description
Air to water heat pump - Yes
Indication if the heater is equipped
with a supplementary heater
- No
Parameters shall be declared for - Low temperature /Medium temperature application
Parameters shall be declared for the average heating season
Outdoor side heat exchanger of air
conditioner/heat pump
- Air
Indoor side heat exchanger of air
conditioner/heat pump
- Water
Type - Compressor driven vapour compression
Driver of compressor - Electric motor
Capacity Control Variable
Indoor heat exchanger Variable outlet
Rated heating capacity (Prated,h) kW 4.44 3.87 6.10 5.37 6.50 5.90
Seasonal space heating energy eciency (ηs,h) % 197 126 194 130 194 134
Seasonal energy eciency ratio heating mode(SCOP) - 5.00 3.23 4.93 3.33 4.92 3.42
Type of energy used - Electricity
Declared heating capacity and coecient of performance for part load at indoor temperature 20°C and outdoor temperature Tj
Outdoor temperature (Tj) = -7°C
Pdh kW 3.9 3.4 5.4 4.7 5.8 5.2
COPd - 3.29 1.97 3.13 2.04 3.14 1.85
Outdoor temperature (Tj) = +2°C
Pdh kW 2.4 2.1 3.3 3.0 3.5 3.2
COPd - 4.80 3.22 4.67 3.21 4.84 3.40
Outdoor temperature (Tj) = +7°C
Pdh kW 1.7 1.4 2.0 2.0 2.3 2.1
COPd - 6.44 3.97 6.63 4.34 5.98 4.50
Outdoor temperature (Tj) = +12°C
Pdh kW 2.2 2.0 2.2 2.0 2.0 2.1
COPd - 9.92 7.24 9.92 7.24 9.67 7.71
Outdoor temperature (Tj) = Bivalent
temperature (Tbiv )
Pdh kW 3.9 3.4 5.4 4.7 5.8 5.2
COPd - 3.29 1.97 3.13 2.04 3.14 1.85
Outdoor temperature (Tj) = Limit
operation temperature (TOL)
Pdh kW 4.3 3.5 5.3 4.5 6.2 5.7
COPd - 2.62 1.68 2.66 1.75 2.66 1.54
Bivalent temperature (Tbiv) heating/Average °C -7 -7 -7 -7 -7 -7
Limit operation temperature (TOL) heating/Average °C -10 -10 -10 -10 -10 -10
Degradation coecient (Cdh) - 0.9 0.9 0.9 0.9 0.9 0.9
Supplementary capacity (PSUP) kW 0.102 0.303 0.729 0.805 0.343 0.179
Annual energy consumption (QHE) kW·h 1824 2457 2539 3312 2732 3536
Model 44 (2.0 HP) 60 (2.5 HP) 80(3.0 HP)
Outdoor unit AHW-044HCDS1 AHW-060HCDS1 AHW-080HCDS1
Indoor unit AHS-044HCDSAA AHS-060HCDSAA AHS-080HCDSAA
Domestic Hot Water HDHWT-
200L30HE
HDHWT-
300L30HE
HDHWT-
200L30HE
HDHWT-
300L30HE
HDHWT-
200L30HE
HDHWT-
300L30HE
Declared prole - L XL L XL L XL
Average climate conditions
Water heating energy eciency (ηwh) % 125 137 125 137 130 137
Water heating energy class - A+ A+ A+ A+ A+ A+
Daily energy consumption kW·h 3.85 5.73 3.85 5.73 3.72 5.67
Annual energy consumption kW·h 820 1223 820 1223 791 1213