Capacity and selection data
3.4 Selection method
To select the outdoor units, it will be necessary to consult and/or use a series of parameters shown in tables and graphics
presented in the di󰀨erent chapters of this handbook. A summarized list is shown below:
For cooling and heating maximum capacities: refer to chapters 3.1&3.2.
For cooling and heating correction factor depending on the piping length: refer to chapters 3.3.1.
For Hi-Therma Monobloc series, heating correction factor owing to use of glycol: refer to chapters 3.3.2.
For heating correction factor owing to deforst operation: refer to chapters 3.3.3.
3.4.1 Selection procedure
For selecting the unit capacity, perform the selection procedure with checking the refrigerant concentration at leakage in order
not to exceed the maximum permissible concentration.
Calculate the building demand load
Select the unit according to the
maximum capacity
(1)
(2)
Check unit capacity with
considering the correction
factors.
unit capacity > building
demand load
Calculate total refrigerant
charge(m
c
)kg
floor area(A
room1
)(m
2
) for installation
Yes
Check total refrigerant
charge(m
c
) 1.84kg
Yes
The selection is completed
No
No
floor area(A
room1
)(m
2
) for
installation
Minimum floor
area(A
min
)(m
2
)
Yes
No
Adjust the unit model and reduce
total refrigerant charge
(3)
(4)
floor area(A
room2
)(m
2
) for adjacent
room
floor area(A
room1
)(m
2
)+ floor
area(A
room2
)(m
2
) Minimum
floor area(A
min
)(m
2
)
Yes
Calculate the minimum opening area
for natural ventilation Anv
min
(m
2
)
between room1 and room2
No
Actual opening area the
calculated minimum opening
area for natural ventilation
Anv
min
(m
2
)
Yes
No
(5)