EasyManua.ls Logo

Hisense AHM-080HCDSAA - Operation Priority

Hisense AHM-080HCDSAA
489 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
214
Control function
10.1.2.2
Operation priority
All the available function will operate alternately with di󰀨erent priority depending on setting. Usually heat pump can operate
alternately between 2 functions.
10.1.2.2.1 Alternate operation between DHW and Space heating/cooling
DHW priority can be set through di󰀨erent ways.
(1) DHW schedule priority
Heat pump will have priority to heat up DHW at [Starting Time 1/2/3/4] with [Setting temperature ON Starting Time 1/2/3/4]
of DHW.
To valid the function of DHW schedule priority set [Status] as [Enabled].
The conguration of this option should be done through the master controller.
Conguration →Auxiliary Function →DHW- Schedule Priority.
Mark Description
Default
Value
Range Steps Units
Status Disabled Disabled/Enabled - -
Starting Time 1 3:00
Disabled-0:00~
24:00
0:10 Time
TDHWS_time1
Setting temperature ON
Starting Time 1
50 40-A 1 °C
Starting Time 2 12:00
Disabled-0:00~
24:00
0:10 Time
TDHWS_time2
Setting temperature ON
Starting Time 2
50 40-A °C
Starting Time 3 16:00
Disabled-0:00~
24:00
0:10 Time
TDHWS_time3
Setting temperature ON
Starting Time 3
50 40-A °C
Starting Time 4 20:00
Disabled-0:00~
24:00
0:10 Time
TDHWS_time4
Setting temperature ON
Starting Time 4
50 40-A °C
Note:
1. When DHW Electric Heater is available ([DHW_hts] set as [Enabled] , refer to 10.3.3), A=75
°C
.
2. When Boiler is available and DHW by Boiler is enabled ([HS] set as [HP+Heater+Boiler] or [HP+Heater+Boiler]
and[DHW_B] set as [Enabled] , refer to 10.6.3), A=60
°C
.
3. circumstance except 1 and 2, A=55
°C
.
(2) Time priority
Set max. DHW operation time with heat pump as [HP ON Max. Time] to limit the max. period time of DHW operation
shift.
Note:
1. Max. DHW operation time of [HP ON Max. Time] will be add extra 70 minutes to heat up DHW in one period time of
DHW operation shift When DHW schedule priority is activated at specic setting Starting Time, DHW boost is activated
(referring to 10.3.6), or DHW Anti-legionella is activated (referring to 10.3.5).
The conguration of this option should be done through the master controller.
Conguration →DHW
Mark Description Default Value Range Steps Units
DHW_HP_tmax HP ON Max. Time 60 20~250~unlimited 1 min
Set Min. space heating/cooling operation time with heat pump as [Min. time Space heating/cooling] to ensure adequate
space heating/cooling operation time in one period time of space heating/cooling operation shift.

Table of Contents

Other manuals for Hisense AHM-080HCDSAA

Related product manuals