10.11 Test Run
10.11.1 Actuator test run
Purpose of the actuator test run is to conrm the operation of the di󰀨erent output signals (e.g., when you select Pump, a
test run of the pump will start).
Select [Actuator_test_Output] of output ports and [Actuator_test_T] of run time to start output ON signal.
The conguration of this option should be done through the master controller.
Conguration →Actuator test run.
Mark Description Default Value Range Steps Units
Actuator_test Start/stop stop Start/stop - -
Actuator_test_T run time 5 5-20 5 min
Actuator_test_Output output test run signal Output15 Output1- Output15 - -
NOTE:
1. Make sure that all air is purged before executing the test run. Also avoid disturbances in the water circuit during the test
run.
2. Be careful to run actuator test of output signal of DHW Electric Heater. DO NOT CAUSE OVERHEAT.
3. Stop the unit before executing the test run.
4. Actuator test run will stop automatically after [run time].
10.11.2 Unit test run
Select run time, mode and function to start unit test run.
The conguration of this option should be done through the master controller.
Conguration →Actuator test run.
Mark Description Default Value Range Steps Units
Start/stop stop Start/stop - -
run time 5 20-120 5 min
mode heating cooling/heating
function C1 C1/C2/DHW/swimming pool - -
NOTE:
1. Make sure that all air is purged before executing the test run. Also avoid disturbances in the water circuit during the test
run.
2. Make sure that minimum water volume is guaranteed in all conditions.
3. Check all electrical, refrigerant and water circuit installation carefully before unit test run.
4. Make sure the minimum required ow rate is reached.