301
Control conguration for OU
11.3.7 Test run
Test run setting should be performed during the outdoor unit stoppage and normal mode. This setting is not available during
other Setting.
To start the Test Run: Press PSW1 and PSW3 for 3 seconds .
To cancel the Test Run: Press PSW1 and PSW3 for 3 seconds.
Note:
1. In case of alarm, T. is replaced by alarm code.
2. The control of Test Run operation is the same as normal operation control.
3. When Test Run is not required, do not forget to exit the Test Run, set T. to 0 or press PSW1 and PSW3.
Test Run and Forced stop of Compressor
Press 1
Test Run
Available
Heating Test
Run Available
Cooling Test Run Available