300
Control conguration for OU
(3) Sound pressure noise and Capacity ratio
When Night Shift Mode is enabled, the sound pressure noise and capacity ratio as follows.
Night_shift_demand(%)
Sound Pressure Noise(dB)
044(2.0HP) 060(2.5HP) 080(3.0HP)
40 35 38 39
50 38 38 39
60 41 41 42
70 43 43 45
80 45 45 46
90 46 46 48
100 47 47 48
(3) Sound pressure noise and Capacity ratio
When Night Shift Mode is enabled, the sound pressure noise and capacity ratio as follows.
Night_shift_demand(%)
Sound Pressure Noise(dB)
044(2.0HP) 060(2.5HP) 080(3.0HP)
40 35 38 39
50 40 42 43
60 41 43 44
70 43 46 47
80 45 48 48
90 47 48 50
100 47 48 50
(2) Frequency Range
When Night Shift Mode is enabled, the maximum Frequency of outdoor unit as follows.
Maximum Frequency(Hz)
Night_shift_demand(%)
Outdoor Unit Capacity
40 50 60 70 80 90 100
044(2.0HP) 20 30 40 50 60 70 80
060(2.5HP) 27 39 51 63 75 86 95
080(3.0HP) 38 47 57 66 76 85 95
11.3.6.2
Night Shift Mode is enabled (Heating operation)
(1) Outdoor Fan
The max step of outdoor fan Fomax:
Fomax = night_shift_demand/100*FoH (Fomax ≥ 6steps)
FoH: See the gure below
Note: FoA: See the gure below.
night_shift_demand Refer to the Section 10.9.7.
-4 0 35
Outdoor Temperature C]
FOH
15
30
11
10