24
Capacity and selection data
3.1.2 Maximum cooling capacity table (kW)
Ambient temperature (°C WB)
5 10 15 20 25
Water
outlet temp
(°C)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
AHW-044HCDS1
+
AHM-044HCDSAA
AHW-044HCDS1
+
AHS-044HCDSAA-23
22
18 7.85 0.94 7.65 0.96 7.24 0.99
15 7.22 0.91 7.14 0.95 7.06 0.98 6.97 1.00 6.89 1.02
10 6.89 0.93 6.78 0.97 6.71 1.01 6.50 1.04 6.27 1.08
7 6.22 1.03 6.12 1.07 5.92 1.12
5 5.61 1.08 5.30 1.17 5.00 1.26
30 35 40 45
Water
outlet temp
(°C)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
22 7.09 1.02 6.58 1.10 6.12 1.18 5.61 1.26
18 6.83 1.06 6.27 1.16 5.71 1.25 5.20 1.32
15 6.40 1.10 5.91 1.19 5.42 1.29 4.93 1.38
10 5.82 1.17 5.37 1.25 4.92 1.36 4.46 1.47
7 5.51 1.23 5.10 1.33 4.64 1.43 4.18 1.52
5 4.69 1.34 4.39 1.43 4.08 1.52 3.77 1.61
Ambient temperature (°C WB)
5 10 15 20 25
Water
outlet temp
(°C)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
AHW-060HCDS1
+
AHM-060HCDSAA
AHW-060HCDS1
+
AHS-060HCDSAA-23
22
18 9.14 1.17 8.93 1.20 8.72 1.23
15 8.58 1.15 8.51 1.19 8.43 1.22 8.36 1.24 8.10 1.27
10 8.12 1.21 7.98 1.24 7.84 1.27 7.71 1.29 7.57 1.33
7 7.35 1.32 7.25 1.34 6.99 1.37
5 6.93 1.38 6.75 1.41 6.37 1.46
30 35 40 45
Water
outlet temp
(°C)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
22 8.51 1.26 7.88 1.33 7.25 1.40 6.62 1.48
18 8.30 1.34 7.56 1.44 6.93 1.54 6.30 1.65
15 7.72 1.37 7.15 1.48 6.58 1.59 6.02 1.70
10 7.07 1.44 6.55 1.55 6.05 1.67 5.53 1.78
7 6.62 1.56 6.30 1.72 5.78 1.86 5.25 2.00
5 5.99 1.67 5.60 1.84 5.22 1.99 4.83 2.12