25
Capacity and selection data
Ambient temperature (°C WB)
5 10 15 20 25
Water
outlet temp
(°C)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
AHW-080HCDS1
+
AHM-080HCDSAA
AHW-080HCDS1
+
AHS-080HCDSAA-23
22
18 10.44 1.35 10.22 1.50 10.01 1.62
15 10.08 1.19 9.94 1.31 9.79 1.44 9.50 1.57 9.36 1.68
10 9.33 1.25 9.14 1.37 8.96 1.50 8.78 1.64 8.50 1.78
7 8.26 1.60 8.06 1.71 7.85 1.83
5 7.99 1.65 7.78 1.77 7.42 1.89
30 35 40 45
Water
outlet temp
(°C)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
22 10.18 1.64 9.57 1.71 8.95 1.77 8.33 1.83
18 9.77 1.71 9.07 1.79 8.23 1.85 7.56 1.93
15 9.11 1.78 8.38 1.86 7.65 1.95 6.98 2.03
10 8.19 1.89 7.61 1.99 7.04 2.11 6.45 2.21
7 7.70 1.95 7.20 2.08 6.69 2.20 6.17 2.33
5 7.23 2.00 6.77 2.12 6.33 2.27 5.76 2.39
NOTE:
CAP: Capacity at compressor maximum frequency. Capacity is valid for dierence between water inlet and water outlet of
3-8°C.
IPT: Total input power.