23
Capacity and selection data
Ambient temperature (°C WB)
-25 -20 -15 -10 -7
Water
outlet temp
(°C)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
AHW-080HCDS1
+
AHM-080HCDSAA
AHW-080HCDS1
+
AHS-080HCDSAA-23
60 5.10 3.43
55 5.76 3.55 6.40 3.17
50 5.34 3.19 6.00 2.99 6.49 2.92
45 4.84 3.07 5.25 2.99 5.71 2.95 6.31 2.86 6.68 2.80
40 5.13 3.05 5.64 2.96 6.20 2.88 6.76 2.80 7.09 2.75
35 5.77 2.83 6.01 2.79 6.33 2.76 7.04 2.64 7.30 2.54
30 6.00 2.81 6.26 2.76 6.53 2.71 7.24 2.58 7.66 2.52
25 6.22 2.81 6.51 2.73 6.81 2.65 7.43 2.53 7.81 2.47
20 6.44 2.79 6.76 2.69 7.09 2.60 7.63 2.49 7.95 2.42
-2 2 7 12 15
Water
outlet temp
(°C)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
60 5.78 3.29 6.32 3.26 7.87 3.22 8.32 3.14 8.39 3.09
55 6.60 3.18 7.16 3.17 9.00 3.10 9.81 2.96 9.86 2.92
50 6.84 3.02 7.44 2.96 9.16 2.87 9.91 2.77 10.04 2.74
45 7.25 2.85 7.71 2.76 9.31 2.66 10.01 2.57 10.22 2.55
40 7.65 2.76 8.10 2.63 10.16 2.58 10.76 2.47 10.89 2.46
35 8.05 2.52 8.48 2.51 11.00 2.50 11.51 2.38 11.56 2.37
30 8.37 2.45 8.95 2.41 11.16 2.40 11.66 2.21 11.71 2.19
25 8.70 2.37 9.41 2.31 11.31 2.29 11.81 2.05 11.86 2.01
20 9.10 2.32 10.01 2.24 11.51 2.04 12.01 1.90 12.17 1.87
20 25 30 35
Water
outlet temp
(°C)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
60 8.59 3.03 8.78 3.00 8.85 2.93 8.86 2.91
55 9.93 2.86 10.01 2.80 10.09 2.73 10.17 2.70
50 10.25 2.69 10.46 2.65 10.67 2.60 10.89 2.55
45 10.56 2.53 10.91 2.50 11.27 2.47 11.35 2.45
40 11.10 2.44 11.31 2.41 11.52 2.38 11.67 2.35
35 11.63 2.34 11.71 2.32 11.79 2.30 11.87 2.28
30 11.78 2.15 11.86 2.11 11.94 2.07 12.02 2.04
25 11.93 1.96 12.01 1.90 12.09 1.85 12.17 1.79
20 12.44 1.83 12.71 1.78 12.99 1.73 13.11 1.69
NOTE:
CAP: Capacity at compressor maximum frequency. Capacity is valid for dierence between water inlet and water outlet of 3-8°C.
IPT: Total input power.
The table above shows the input power (IPT) at maximum capacity (CAP). Most of the time, the unit will run at partial load, so that the actual
input power will be lower.
Measuring procedure follows EN-14511.