215
Control function
Note:
1. Min. space heating/cooling operation time of [Space_HP_tmin] will be limited to 20 minutes to accelerate shift of DHW
operation When DHW schedule priority is activated at specic setting Starting Time, DHW boost is activated (referring to
10.3.6), or DHW Anti-legionella is activated (referring to 10.3.5).
The conguration of this option should be done through the master controller.
Conguration →Heat Pump→ Heat Pump Priority
Mark Description Default Value Range Steps Units
Space_HP_tmin Min. time Space heating/cooling 60 20-240 1 min
(3) DHW set temperature priority
Set Hysteresis between DHW set temperature and DHW temperature as [DHW Setting Temperature Dierential Temp] to
start DHW operation shift.
Note:
1. Hysteresis between DHW set temperature and DHW temperature as [DHWS_shift_di] will be limited to accelerateshift
of DHW operation When DHW schedule priority is activated at specic setting Starting Time, DHW boost is activated
(referring to 10.3.6), or DHW Anti-legionella is activated (referring to 10.3.5).
The conguration of this option should be done through the master controller.
Conguration →Heat Pump→ Heat Pump Priority
Mark Description Default Value Range Steps Units
DHWS_shift_di DHW Setting Temperature Dierential Temp 10 6-20 1 °C
Alternate operation between Space heating/cooling and DHW
.
● Meet all following conditions to start DHW operation shift (DHW Switch ON).
(1) TDHW ≤ TDHWS - DHWS_shift_di or TDHW1 ≤ TDHWS- DHWS_shift_di if TDHW1 is valid.
(2) Period time of space heating/cooling operation shift is more than [Space_HP_tmin] or space heating/cooling has no
demand.
● Meet one of following conditions to start space heating/cooling operation shift (space heating/coolingSwitch ON).
(1) TDHW is met and TDHW1 is met if TDHW1 is valid.
(2) Max temperature of THPSTOP is reached. (THPSTOP refers to 10.3.4).
(3) Period time of DHW operation shift is more than [DHW_HP_tmax].
Time
temp
time1=04:00
TDHWS- DHWS _shift_diff
TDHWS
Space_HP_tmin
time2=19:00
THPSTOP
Space heating/cooling operation(Switch ON)
DHW operation(Switch ON)
DHW Electric Heater operation
DHW schedule priority
Starting Time1
DHW_HP_tmax
DHW boost
DHW schedule priority
Starting Time2
TDHWS_time1
TDHWS_time2
TDHWS_boost
DHWEH
TDHW/TDHW1