225
Control function
10.2.2.1.2 Water ECO oset
● Function
Use a reduced oset for water temperature setting. By using this function, current water temperature setting is reduced by
the indicated parameter.
The conguration of this option should be done through the master controller
Conguration → Space heating →Cycle 1
Mark Description Default Value Range Steps Units
c1_wate_Eco water Eco Disabled Disabled/Enabled
c1_wate_h_Ecoofs Eco oset 2 -10~10 1 °C
Conguration → Space heating →Cycle 2
Mark Description Default Value Range Steps Units
c2_wate_Eco water Eco Disabled Disabled/Enabled
c2_wate_h_Ecoofs Eco oset 2 -10~10 1 °C
● Function activation
ECO oset function is active for each Cycle by dierent options:
(1) [water Eco] of specic Cycle on Conguration set as [Enabled]
(2) Optional input signal can be congured as function of Cycle 1 ECO mode / Cycle 2 ECO mode / Cycle 1 and 2 ECO
mode and close the corresponding input terminal. refer to 10.10.1.
(3) [water Eco] of specic Water Cycle from interface of Water Cycle on master controller is pushed ON.
10.2.2.1.3 Compensation from Room thermostat
There are max. 4 room thermostats that can be incorporated to each Water Cycle (Cycle 1 and Cycle 2). Compensate
water temperature setting by room temperatures and room temperature settings on the specic Cycles (Cycle 1 & 2) to
operate space heating/cooling eciently.
This function is available with the following possible combinations:
● Rooms function on Master controller is selected as room thermostat. Optional Auxiliary sensor on PCB1 of indoor unit
can be congured as function of Room_amb1...7 and be selected as Room temperature detection. Refer to 10.10.
● Slave_Wired room controller can be selected as room thermostat.
When Room compensation is enabled, the calculated set point is adjusted according on the dierence between the room
temperature and room setting temperature. The amount of room inuence can be adjusted by the room temperature
compensation factor setting.
To increase or decrease the amount of room compensation, the room compensation factor should be adjusted.
(1) Cycle 1
The conguration of this option should be done through the master controller
Conguration → Space heating → Cycle 1→Room temperature Compensation
Mark Description Default Value Range Steps Units
Rfacth_c1 Compensation factor 2 OFF-1-5 1 °C
Maxfacth _c1 Max Compensation value 10 0~10 1 °C
Minfacth _c1 Min Compensation value -10 -10~0 1 °C
Compenh_c1= Rfacth_c1 × Maximum dierence of room setting temperature and room temperature for
Thermo On Rooms on Cycle 1
Minfacth _c1 ≤ Compenh_c1 ≤ Maxfacth _c1