Specifications
kV, Common Mode and Differential Mode. The instrument is
capable of meeting these test levels with no component failures,
no reset, and no incorrect outputs.
Radio Frequency
Interference (RFI)
Immunity: No effect on performance from a 5 W walkie-talkie
operated at 151 or 450 MHz, one meter from the controller.
Environmental and Operating Conditions
Parameter Recommended Rated Operative
Limits
Transportation
and Storage
Ambient
Temperature
25 ± 3 °C
77 ± 5 °F
0 to 55 °C
32 to 131
°F
0 to 55 °C
32 to 131 °F
–40 to 66 °C
–40 to 151 °F
Relative Humidity 10 to 55* 5 to 90* 5 to 90* 5 to 95*
Vibration:
Frequency (Hz)
Acceleration (g)
0
0
1
30
5
30
20
30
Mechanical Shock:
Acceleration (g)
Duration (ms)
0
0
1
30
5
30
20
30
Line Voltage (Vdc) +24 ± 1 24 21.6 to 26.4 - -
Line Voltage (Vac)
100 to 240 Vac
24 Vac
120 ± 1
240 ± 2
24 ± 1
100 to 240
24
90 to 264
21.6 to 26.4
- -
- -
- -
Frequency (Hz)
(For Vac)
50 ± 0.2
60 ± 0.2
50
60
50 ± 2
60 ± 2
- -
- -
Altitude 2000 meters
* The maximum moisture rating only applies up to 40 °C (104 °F). For higher
temperatures, the RH specification is derated to maintain constant moisture content.
Chapter 3 - Installation

Table of Contents

Other manuals for Honeywell UDC2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC2800 and is the answer not in the manual?

Honeywell UDC2800 Specifications

General IconGeneral
Control ModesPID, ON/OFF, Manual
MountingPanel Mount
DisplayDual 4-digit LED
Input TypesThermocouple, RTD, mA, mV, V
Output TypesRelay
Power Supply100-240 VAC, 50/60 Hz
CommunicationRS-485 Modbus RTU
Enclosure RatingNEMA 4X

Related product manuals