38
Specifications
kV, Common Mode and Differential Mode. The instrument is
capable of meeting these test levels with no component failures,
no reset, and no incorrect outputs.
Radio Frequency
Interference (RFI)
Immunity: No effect on performance from a 5 W walkie-talkie
operated at 151 or 450 MHz, one meter from the controller.
Environmental and Operating Conditions
Parameter Recommended Rated Operative
Limits
Transportation
and Storage
Ambient
Temperature
25 ± 3 °C
77 ± 5 °F
0 to 55 °C
32 to 131
°F
0 to 55 °C
32 to 131 °F
–40 to 66 °C
–40 to 151 °F
Relative Humidity 10 to 55* 5 to 90* 5 to 90* 5 to 95*
Vibration:
Frequency (Hz)
Acceleration (g)
0
0
1
30
5
30
20
30
Mechanical Shock:
Acceleration (g)
Duration (ms)
0
0
1
30
5
30
20
30
Line Voltage (Vdc) +24 ± 1 24 21.6 to 26.4 - -
Line Voltage (Vac)
100 to 240 Vac
24 Vac
120 ± 1
240 ± 2
24 ± 1
100 to 240
24
90 to 264
21.6 to 26.4
- -
- -
- -
Frequency (Hz)
(For Vac)
50 ± 0.2
60 ± 0.2
50
60
50 ± 2
60 ± 2
- -
- -
Altitude 2000 meters
* The maximum moisture rating only applies up to 40 °C (104 °F). For higher
temperatures, the RH specification is derated to maintain constant moisture content.
Chapter 3 - Installation