EasyManua.ls Logo

Honeywell UDC2800 - Calibration Overview

Honeywell UDC2800
432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Overview
Introduction
This section describes the field calibration procedures for Input 1
and Input 2.
n
All input actuations in every UDC2800 controller are fully factory-
calibrated and are ready for configuration by the user.
n
Field Calibration can improve the accuracy of the Controller if
necessary for a particular application.
CAUTION: The field calibration will be lost if a change in input
type configuration is implemented at a later time. The original
factory calibration data remains available for later use after a
field calibration is done. See Restore Input Factory Calibration
for more information.
Calibration Steps
Use the following steps when calibrating an input.
Step Action
1 Find the minimum and maximum range values for your PV input range from
the table Voltage, Milliamp and Resistance Equivalents for Input Range Values.
2 Disconnect the field wiring and find out what equipment you will need to
calibrate.
3 Wire the calibrating device to your controller according to the set up wiring
instructions for your particular input (See Input 1 or 2 Set Up Wiring for more
information.).
4 Follow the calibration procedure given for Input #1 or Input #2 (See Input 1 or
2 Calibration Procedure for more information.).
227
Chapter 6 - Input Calibration

Table of Contents

Other manuals for Honeywell UDC2800

Related product manuals