Input 2 Set Up Group
Introduction
This data deals with various parameters required to configure Input
2.
Function Prompts
Table 4-11: Input 2 Group Function Prompts
Function
Prompt
Selections or
Range of
Setting
Parameter Definition
Input 2 Type Input 2 Actuation Type – This selection determines
what actuation you are going to use for Input 2
ATTENTION: Changing the input type will
result in the loss of Field Calibration values
and will restore Factory Calibration values
Selecting Position Proportional Control in the
Output Setup Group forces Input 2 to the
Slidewire Selection.
Disable Disables Input
TC B B Thermocouple
TC E High E Thermocouple High
TC E Low E Thermocouple Low
TC J High J Thermocouple High
TC J Mid J Thermocouple Med
TC J Low J Thermocouple Low
TC K High K Thermocouple High
TC K Mid K Thermocouple Med
TC K Low K Thermocouple Low