SP Program 7
Table 12-27: Setpoint Program 7
Parameter Description
Register Address
Access Description
Hex Decimal
Time Units 20BA 48379 R Bit Packed
Bit 0: seconds
1: minutes
2: hours
3-15: Unused
NOTE:
UDC2800
does not
support
seconds
Ramp Units
20BB 48380 R Bit Packed
Bit 0:0: Time; 1:
Rate Bit
1-15: Unused
Program End Segment (Program 1
only)
20BD
48382
R/W Bit Packed
Bit 0: 1: 2
1: 1: 4
2: 1: 6
3: 1: 8
Program Termination State
20BE 48383 R/W Bit Packed
Bit 0: 0: Last SP
(Hold at last SP in
program)
1: F'SAFE (Manual
mode, failsafe
output)
419
Chapter 12 - Standard Modbus Read, Write and Override Parameters