Output Set Up Group
Introduction
This group deals with various output types in the controller, the
Digital Output Status and the Current Output operation.
ATTENTION: The Tuning Group is automatically configured to
have two PID sets when a Duplex Control Algorithm is selected.
Function Prompts
Table 4-9: OUTPUT Group Function Prompts
Function
Prompt
Selections or Range
of Setting
Parameter Definition
Output
Algorithm
The output algorithm lets you select the type
of output you want. Not applicable with
Control algorithm prompt Three Position Step.
Selections are hardware dependent. For
example, if the controller does not have a
current output, then none of the prompts for
Output Algorithms that need a current output
will appear. Likewise, if the controller does not
have a relay output, then none of the prompts
that need a relay output will appear.
ATTENTION: For all Duplex Output
forms, PID heat parameters apply for
controller output greater than 50 %; PID
cool parameters apply for controller
output less than 50%.
Time Simplex This output algorithm uses Digital Output 1
for Time Proportional Control. The output is
updated per the sampling rate selection. Time
Proportional Output has a resolution of 3
msec. Cycle Time is adjustable from 1 to 120
seconds.