EasyManua.ls Logo

Honeywell UDC2800 - Accutune Setup Group

Honeywell UDC2800
432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Accutune Set Up Group
Introduction
Accutune III automatically calculates GAIN, RATE, and RESET TIME
(PID) tuning constants for your control loop. When initiated on
demand, the Accutune algorithm measures a process step response
and automatically generates the PID tuning constants needed for no
overshoot on your process.
Fuzzy , Fuzzy Overshoot Suppression: When enabled, this
configuration will suppress or eliminate any overshoot that may
occur as a result of the existing tuning parameters, as the PV
approaches the setpoint.
Tune, Demand Tuning: The tuning process is initiated through the
operator interface keys or via a digital input (if configured). The
algorithm then calculates new tuning parameters and enters them in
the tuning group. Tune will operate with PIDA, PIDB, PD+MR and
Three Position Step Control algorithms.
Simplex Tuning is used when a Simplex Control Algorithm is
configured and uses the current SP value and alters the output over
the Output Limit Range.
Duplex Tuning is used when a Duplex Control Algorithm is
configured. To perform a Duplex Tune, Two Local Setpoints must be
configured. See Control Set Up Group for more information.
91
Chapter 4 - Configuration

Table of Contents

Other manuals for Honeywell UDC2800

Related product manuals