Parameter Description
Register Address
Access Description
Hex Decimal
Bit 10: Unused
Bit 11: 1 = Run Status, 0
= Hold Status
Bit 12: 1 = Any Digital
Input Active
Bit 13: 1 = Any Alarm
Active
Bit 14: Unused
Bit 15: 1 = Guaranteed
Soak Deviation (Out of
Limit), soak segment is
stuck
Analog Input Register Map
Use the identifying codes listed in the following table to read the
specific items.
A Write request for these codes will result in an Error message.
Table 12-7: Analog Input Parameters
Parameter Description
Register Address
Access Description
Hex Decimal
Analog Input 1 1800 46145 R Floating Point in
Engineering Units.
Analog Input 2 1802 46147 R Floating Point in
Engineering Units.
391