EasyManuals Logo

Honeywell UDC2800 User Manual

Honeywell UDC2800
432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #428 background imageLoading...
Page #428 background image
Data Field:
In a normal response, the responder may return data or statistics in
the data field. In an exception response, the responder returns an
exception code in the data field. This defines the responder condition
that caused the exception.
Query
Example: Internal responder error reading 2 registers starting at
address 1820h from responder at responder address 02.
02 03 18 20 00 02 CRC CRC
Response
Example: Return MSB in Function Code byte set with responder
Device Failure (04) in the data field.
02 83 04 CRC CRC
Table 13-1: Modbus RTU Data Layer Status Exception Codes
Exception
Code
Definition Description
01 Illegal
Function
The message received is not an allowable action for the
addressed device.
02 Illegal Data
Address
The address referenced in the function-dependent data
section of the message is not valid in the addressed device.
03 Illegal Data
Value
The value referenced at the addressed device location is no
within range.
428
Chapter 13 - Modbus Communication Exception Codes

Table of Contents

Other manuals for Honeywell UDC2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC2800 and is the answer not in the manual?

Honeywell UDC2800 Specifications

General IconGeneral
Control ModesPID, ON/OFF, Manual
MountingPanel Mount
DisplayDual 4-digit LED
Input TypesThermocouple, RTD, mA, mV, V
Output TypesRelay
Power Supply100-240 VAC, 50/60 Hz
CommunicationRS-485 Modbus RTU
Enclosure RatingNEMA 4X

Related product manuals