SP Ramp/Program Set Up Group
Introduction
Set Point Ramp, Set Point Rates and Set Point Programs can be
configured in this group.
n
A single Setpoint Ramp (SP Ramp) can be configured to occur
between the current local setpoint and a final local setpoint over a
time interval of from 1 to 255 minutes.
NOTE: SP Ramp only appears when SP Program is disabled.
n
A Set Point Rate (SP Rate) lets you configure a specific rate of
change for any local setpoint change.
NOTE: SP Rate only works in Auto mode.
NOTE: SP Rate operates only when both SP Ramp and SP
Programing are in Hold mode or when both SP Ramp and
SP Programming are disabled.
n
Up to 8 Set Point Programs (SP Program) can be configured. Each
SP Program has 8 segments.
NOTE: SP Program only appears when SP Ramp is disabled.
You can configure SP Program 1 in this group, and configure
other 7 SP programs in the corresponding set up groups. See SP
Program 2 Set Up Group ~ SP Program 8 Set Up Group for more
information.
You can start and stop the ramp / program using the RUN/HOLD key
(Setup and Increment keys).
NOTE: When SP ramp / program is running or held but not
terminated, the configuration of Ramp / Program is
unchangeable.
A ramp segment in SP ramp / program completes when either of the
following two condition is satisfied:
81