250
Step Operation Press Result
7 Exit the
Calibration
Mode
Function
key
The controller will store the 100 % value.
Lower
Display key
To exit the calibration mode
Restore Output Factory Calibration
Introduction
The factory calibration constants for the Current and Auxiliary
Outputs are stored in its non-volatile memory. Thus, you can quickly
restore the “Factory Calibration” for those outputs by simply
changing the CO Range setting for that output to the other setting
and then changing it back to the original type.
Refer to table below for procedure.
ATTENTION: A restored factory calibration overwrites any
previous field calibration done for the output. Protect your field
calibration from accidental overwrites by configuring the
appropriate LOCKOUT selection after calibration. See
Configuration for more information.
Chapter 7 - Output Calibration

Table of Contents

Other manuals for Honeywell UDC2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC2800 and is the answer not in the manual?

Honeywell UDC2800 Specifications

General IconGeneral
Control ModesPID, ON/OFF, Manual
MountingPanel Mount
DisplayDual 4-digit LED
Input TypesThermocouple, RTD, mA, mV, V
Output TypesRelay
Power Supply100-240 VAC, 50/60 Hz
CommunicationRS-485 Modbus RTU
Enclosure RatingNEMA 4X

Related product manuals