In the Control set up list, do not select SP Tracking as PV or
Remote SP.
n
In the SP Ramp set up list, do not select SP Rate as Enable.
n
In the Algorithms set up list, do not select Control Algorithm as
PID B, On-Off, or Three Position Step.
n
In the Display menu, when PID Set # is displayed, DO NOT
change the selection.
Operation
Operate the Auto/Manual Station as follows:
Set the Local Setpoint 2 to 0% of the Input 2 range.
There features work with the Auto/Manual Station.
n
In the SP Ramp set up list, SP Program (acts on SP1 for backup
operation).
n
In the SP Ramp set up list, SP Ramp (acts on SP1 for backup
operation).
n
In the Control set up list, Action Direction as Direct or Reverse for
the backup PID A operation).
n
The PD+Manual Reset action is forced to be Direct as required for
the pass through of the output signal.
Alarm Setpoints
Introduction
An alarm consists of a relay contact and an operator interface
indication. The alarm relay is de-energized if setpoint 1 or setpoint 2
is exceeded.
The alarm relay is energized when the monitored value goes into the
allowed region by more than the hysteresis.
The relay contacts can be wired for normally open (NO) energized or
normally closed (NC) de-energized using internal jumper placement.
There are four alarm setpoints, two for each alarm. The type and state
(High or Low) is selected during configuration.
207
Chapter 5 - Monitoring and Operating the Controller

Table of Contents

Other manuals for Honeywell UDC2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC2800 and is the answer not in the manual?

Honeywell UDC2800 Specifications

General IconGeneral
Control ModesPID, ON/OFF, Manual
MountingPanel Mount
DisplayDual 4-digit LED
Input TypesThermocouple, RTD, mA, mV, V
Output TypesRelay
Power Supply100-240 VAC, 50/60 Hz
CommunicationRS-485 Modbus RTU
Enclosure RatingNEMA 4X

Related product manuals