EasyManua.ls Logo

Honeywell UDC2800 - Page 208

Honeywell UDC2800
432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
208
Alarm Setpoints Display
Table 5-17: Procedure for Displaying Alarm Setpoints
Step Operation Press Result
1 Select
Alarms
Set-up
Group
Setup key or
Increment key or
Decrement key
Until you see Alarms set up group
2 Select the
Alarm
Setpoint
Values
Function key Enter in the first function prompt A1S1 Type.
Increment key or
Decrement key
Until you see the required Alarm setpoint.
A1S1 Value = Alarm 1, Setpoint 1 Value
A1S2 Value = Alarm 1, Setpoint 2 Value
A2S1 Value = Alarm 2, Setpoint 1 Value
A2S2 Value = Alarm 2, Setpoint 2 Value
To successively display the alarm setpoints
and their values. Their order of appearance is
shown below.
Lower Display = (the alarm setpoint value)
Range values are within the range of the
selected parameters except:
Deviation value = PV Span
Events (Event On/Event Off) value = Event
Segment Number
PV Rate of Change = The amount of PV
change in one minute in engineering units.
Loop Break Alarms (Loop Break)= The timer
value may be changed only for controllers
configured for ON/OFF control.
NOTE: With Three position step control,
alarms set for “output” will not function.
NOTE: Manual, Remote Setpoint, and
Failsafe selections do not have setpoint
values.
Chapter 5 - Monitoring and Operating the Controller

Table of Contents

Other manuals for Honeywell UDC2800

Related product manuals