5. Issue the show chassis power detail command to check the power usage in watts for
hardware components such as FPCs, fan trays, Routing Engine and control board,
and SIB, CCG, and craft interface.
user@host> show chassis power detail
Chassis Power        Used(W)
Total Power            4890
  PDU 0                2447
    PSM 0              1292
    PSM 1               702
    PSM 2               210
    PSM 3               243
  PDU 1                2443
    PSM 0              1291
    PSM 1               685
    PSM 2               196
    PSM 3               271
Item                 Used(W)
  Fan Tray 0            194
  Fan Tray 1            482
  Fan Tray 2            488
  RE0/CB0               107
  RE1/CB1               108
  SIB/CCG/FPD            63
  FPC 0                   0             
  FPC 1                   0
  FPC 2                   0
  FPC 3                   0
  FPC 4                   0
  FPC 5                   0
  FPC 6                   8
  FPC 7                   0
6. Verify that the source circuit breaker has the proper current rating.
NOTE: All inputs on a DC PDU in slot PDU0 must be powered bydedicated
power feeds derived from feed A, and all inputs on a DC PDU in slot PDU1
must be powered by dedicated power feeds derived from feed B. This
configuration provides the commonly deployed A/B feed redundancy for
the system.
7. Verify that the DC power cables from the power source to the PDU are not damaged.
If the insulation is cracked or broken, immediately replace the DC power cable.
8. If you cannot determine the cause of the problem or need additional assistance, see
“Contacting Customer Support” on page 275.