Display Error and possible cause Remote dis-
play
Read cong failed The saved conguration and calibration data cannot be
read.
- Restore the data saved in a backup (in the menu [System
maintenance] - [Restore] - [SD card] ) to the device
(see Chapter 6.2.1).
- First set the weighing electronics (e.g. [internal weighing
point]) to [not assigned], save, and then reassign.
Error A
9.4 Error messages at PR-Net weighing point
Display Error and possible cause Remote dis-
play
Wrong conguration No IP address or no host name available. Error 13
9.5 Error messages at "Mettler-Scale" weighing point
Display Error and possible cause Remote dis-
play
Arith. error Internal arithmetic overow:
- Parameters/calibration values do not match those of the
Mettler-Scale.
Error 1
9.6 Warnings when assigning a weighing point
Weighing point C @admin
Weighing point not assigned
Default Save
STOP
WARNING!
Changing the allocation of the fluid counter
after xBPI scale to Weighing point C
clears all adjustment data
and parameters for weighing point C.
Cancel Continue
After a weighing point has been assigned, it is set to the default values and saved.
This message appears if a weighing point is set to [not assigned].
Process Controller Maxxis 5 PR 5900 9 Error messages
Minebea Intec EN-366