[I/Os]
Selection: 8 to 256 Byte I/O
[Fieldbus operating mode]
Selection: Only application, scale interface, SPM interface
[Only application] is selected for project applications.
[Scale interface] is selected if scale and application values are exchanged via the
eldbus interface.
[SPM interface] is selected if the SPM needs to be accessed via the eldbus interface.
[Scale interface]
Selection: disabled; WP A (equals 8 bytes); WP A, B (equals 16 bytes); WP A, B, C
(equals 24 bytes); WP A, B, C, D (equals 32 bytes)
Network-based eld bus protocols:
[IP address]
Input: via keyboard
[Subnet mask]
Input: via keyboard
Probus-DP:
[Probus-DP address]
Input: via keyboard
4.6.1 Fieldbus settings for the SPS
Conguration of the interface is carried out in the device under [System setup] - [Fieldbus
parameters], see Chapter 4.6.
Requirements:
- The relevant eldbus card has been installed, see PR 5900 installation manual.
- The parameters have been selected and saved according to the weighing points
(1× WP = 8 byte I/O), see Chapter 4.6.
- The corresponding device description data has been loaded to the SPS development
environment, see PR 5900 installation manual.
- ProBus-DP: xx_xx.gsd
- DeviceNet: xx_xx.eds
- ProNet I/O: GSDML-xx-xx-xx-xx.xml
- EtherNet-IP: xx_xx_xx.eds
Card test:
The eldbus cards have LEDs that display their status, see PR 5900 installation manual.
All inputs and outputs are displayed in the menu [Operating] - [System maintenance] -
[Test hardware] - [I/O cards test] - [Option FB].
3. Press the [Save] soft key to save the settings.
4 System setup Process Controller Maxxis 5 PR 5900
EN-89 Minebea Intec