VISOR
®
Communications manual
Teach detector (BINARY)
Telegrams: Availability and supported interfaces (Page 85)
Overview telegrams (Page 81)
Teach detector (binary) request string to sensor
Byte no. Data type Content Meaning
1 - 4 Unsigned Int 0x08 Telegram length
5 Unsigned Char 0x18 Teach detector
6 Unsigned Char 0xXX
0 = Alignment
>= 1 Detectors
7 Unsigned Char 0xXX
0: Temporary
1: Permanent
8 Unsigned Char 0xXX
0 = No trigger
1 = Trigger
Teach detector (binary) response string from sensor
Byte no. Data type Content Meaning
1 - 4 Unsigned Int 0x00 Telegram length
5 Unsigned Char 0x18 Teach detector
6 - 7 Unsigned Short 0xXX Error codes (Page 88)
Additional information:
Accepted in run mode: Yes
Accepted in config mode: No
Accepted when Ready is low: Yes
Status of Ready signal during
processing:
No change
Supported interfaces:
Telegrams: Availability and supported interfaces
(Page 85)
06814859 - 1/24/2019-00 Page 222 EN