EasyManua.ls Logo

SENSTAR OmniTrax - Sensor Cable Start Points; Aligning the Lead-in Cables

SENSTAR OmniTrax
252 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Preparation of trenches
OmniTrax Product Guide Page 115
Sensor cable start points
At sensor cable start points:
the lead-in and detecting cables must cross each other at a 90° angle
the detecting cable is installed above the lead-in cable, and the detecting and lead-in cables
must NOT touch at the crossover
for cables buried in soil there must be a vertical separation of at least 23 cm (9 in.) over a short
distance, i.e., the bottom cable (lead-in) must be buried at least 46 cm (18 in.) deep, with the
detecting cable buried at 23 cm (9 in.)
for cables in hard surface slots there must be a vertical separation of at least 2.5 cm (1 in.)
over a short distance, i.e., the bottom cable (lead-in) must be installed in a 9.5 cm (3¾ in.)
deep slot, with the detecting cable installed above it at 6 cm (2¼ in.)
Detecting cable crossover
If two detecting sensor cables cross, you must raise one cable and lower the other. Change the
burial depths over approximately 1 m (3.3 ft.) using a very gentle slope. For burial in soil, the
required separation between detecting sensor cables is 23 cm (9 in.). For slot installation the
required separation is 4 cm (1.5 in.). The two detecting cables must cross at a 90º angle.
Aligning the lead-in cables
1. Unroll the lead-in cable and lay it in the trench or slot between the start point and the
processor location.
2. Line up the two red bands on the sensor cables side-by-side at the designated start point.
3. Temporarily anchor the sensor cable at the red mark.
Figure 79: Detecting cable / lead-in cable crossover
Figure 80: Detecting sensor cable crossover in soil
Note Use a stake or a flag to mark the location of the red bands on the
ground’s surface.
sensor cable
top view
lead-in cable
90°
sensor
cable
side view
lead-in cable
ground level
46 cm (18 in.)
minimum
a
detecting cable and lead-in cable
must cross at a 90° angle
a = min. 23 cm (9 in.) in soil
a = min. 2.5 cm (1 in.) in concrete/asphalt
11.5 cm (4.5 in.)
23 cm (9 in.)
23 cm (9 in.)
11.5 cm
1 m (3.3 ft.)
ground
level

Table of Contents

Related product manuals