Appendix C — Specifications Library Specifications
December 2019 User GuideSpectra T200, T380, and T680 Libraries
537
Environmental Specifications
This section describes environmental specifications for the library. Do not
place the library on a carpeted floor or anywhere else that poses risk for
static discharge that could damage the library and its drives.
The library is equipped with internal fans that operate as much as is
necessary for the number of DBAs installed. The fans keep the library’s
internal temperature within specifications as long as the data center
environment is within specifications.
6807 Japan NEMA L6-20P
6808
a
Continental Europe CEE(7)VII
8665 United Kingdom,
Continental Europe
IEC 60309
a. For non-locking supply-end plugs, an additional grounding wire from the chassis to earth ground is
required.
Part
Number
Country of Use Plug Style Appearance
WARNING
The library must be installed in the rack that is delivered with the library, or if none
is included, in a standard 19-inch (48-cm), four-post rack. A two-post rack cannot
support the weight of the library. Ensure your floor has adequate structural
integrity, and follow the rack manufacturer's instructions when installing and
securing the rack.
Caution
When the library is moved from a cold environment to a warm environment, it
should not be powered on for at least 24 hours. This adjustment period prevents
condensation damage.