Appendix
12.4.1 Using a Braking Resistor Unit
12 - 8
12.4 Wiring Examples
12.4.1 Using a Braking Resistor Unit
CIMR-G5A20P4 to -G5A27P5 (200 V class Inverters of 0.4 to 7.5 kW)
CIMR-G5A40P4 to -G5A4015 (400 V class Inverters of 0.4 to 15 kW)
Short-circuit bar
¨1
DC Reactor to
improve input
power factor
(Optional)
Braking Resistor overheating contacts
(Thermal overload relay trip contacts)
Braking Resistor Unit
*3
VS-616G5
MCCB
3-phase power
200 to 230 V
50/60 Hz
or
380 to 460 V
50/60 Hz
R
MC
R (L1)
S
S (L2)
T T (L3)
*1 400/200 V
THRX
OFF
ON
MC
SA
Overload relay trip contact
of Braking Resistor Unit
12
MC
TRX
TRX
20 18
Fault contacts
A sequence is required to turn
OFF the power supply for the
thermal overload relay trip con-
tacts of the Braking Resistor Unit.
¨2B1B2
SA
SA
THRX
U (T1)
V (T2)
W (T3)
Motor
IM
(200 V class Inverters: Ground
to 100 max., 400 V class In-
verters: Ground to 10 max.)
12
BP
MC
©
*2
*1 A transformer is not required for 200 V class Inverters.
*2 Remove the short-circuit bar (normally connected) from between terminals
¨1 and ¨2 when connecting a DC Reactor (Optional).
*3 Disable stall prevention during deceleration by setting L3-04 to “0” when us-
ing a Braking Resistor Unit. The motor may not stop within the deceleration
time if this setting is not changed.
12.4.2 Using a Braking Unit and Braking Resistor Unit
CIMR-G5A2011, -G5A2015 (200 V class Inverters of 11 kW, 15 kW)
U (T1)
©
V (T2)
W (T3)
MCCB
R
MC
R (L1)
S
S (L2)
T
T (L3)
THRX
OFF
ON
MC
SA
Overload relay trip contact
of Braking Resistor Unit
1
2
MC
TRX
TRX
20 18
Fault contacts
SA
SA
THRX
3
Braking Unit
34
Motor
IM
(Ground to 100 max.)
¨1
DC Reactor to
improve input
power factor
(Optional)
Braking Unit
(Optional)
¨2 ¨3
¨
¨
0
P
B
Braking Resistor Unit
*2
(Optional)
1
2
Braking Resistor overheating contacts
(Thermal protector trip contacts)
Level
detector
3-phase power
200 to 230 V
50/60 Hz
3
4
VS-616G5
©
MC
A sequence is required to turn
OFF the power supply for the ther-
mal overload relay trip contacts of
the Braking Resistor Unit.
*1
*1 Remove the short-circuit bar (normally connected) from between terminals
¨1and¨2 when connecting a DC Reactor (Optional).
*2 Disable stall prevention during deceleration by setting L3-04 to “0” when us-
ing a Braking Resistor Unit. The motor may not stop within the deceleration
time if this setting is not changed.
Short-circuit bar
©
0
Forward Run/Stop
Forward run command
(forward run when closed)
Reverse Run/Stop
Reverse run command
(reverse run when closed)
External fault