EasyManuals Logo

YASKAWA CIMR-G5A Series User Manual

YASKAWA CIMR-G5A Series
355 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #169 background imageLoading...
Page #169 background image
7.2 V/f Control without PG
7-15
J
Motor Ironcore Loss with Torque Compensation:E2-10 (for SPEC: F)
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
E2-10
Motor ironcore loss
with torque com-
pensation
×
0 to 65535
W
14
A A
× ×
D
The default setting depends upon the Inverter capacity. The above table shows the settings for 200V
class, 0.4 kW Inverter. (See page:8 - 47)
D
The motor ironcore loss is set in “W” units.
D
Normally, the settings do not need to be altered. However, if the Inverter and motor capacities are vast-
ly different, set the E2-10 value for the same Inverter capacity as the applicable motor. (See page:
8 - 47)
7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIMR-G5A Series and is the answer not in the manual?

YASKAWA CIMR-G5A Series Specifications

General IconGeneral
BrandYASKAWA
ModelCIMR-G5A Series
CategoryInverter
LanguageEnglish

Related product manuals