User Constants
8.2.6 Terminal Constants: H
8-30
J
Multi-function Outputs: H2
C
S
Change
Control Methods
Constant
Number
Name Display
Setting
Range
Factory
Setting
Change
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
H2-01
Multi-function input
(terminal 9-10)
Terminal 9 Sel 0to37 0
×
B B B B
7-77
H2-02
Multi-function input
(terminal 25-27)
Terminal 25 Sel 0to37 1
×
B B B B
7-77
H2-03
Multi-function input
(terminal 26-27)
Terminal 26 Sel 0to37 2
×
B B B B
7-77
Multi-function Output Functions
Control Methods
Setting
Value
Function
V/f
V/f
w/
PG
Open
loop
Vec-
tor
Flux
vec-
tor
Page
0
During run (ON: run command is ON or voltage is being output)
f f f f
7-78
1
Zero-speed
f f f f
7-78
2
Frequency agree 1: (Detection width L4-02)
f f f f
7-90
3
Desired frequency agree 1
[ON(: Output frequency = ±L4-01, detection width in L4-02) and during frequency agree]
f f f f
7-90
4
Frequency (Four) detection 1 (ON: +L4-01 output frequency L4-01, detection width in L4-02)
f f f f
7-90
5
Frequency (Four) detection 2
(ON: Output frequency +L4-01 or output frequency L4-01, detection width in L4-02)
f f f f
7-90
6
Inverter operation ready READY: After initialization, no faults
f f f f
7
During DC bus undervoltage (UV) detection
f f f f
8
During baseblock (ON: during baseblock)
f f f f
9
Frequency reference selection (ON: Frequency reference from Operator)
f f f f
A
Run command selection (ON: Run command from Operator)
f f f f
B
Overtorque detection 1 NO (NO contact: Overtorque detection at ON)
f f f f
7-94
C
Loss of frequency reference (Effective when operation selection is “1” for L4-05 frequency reference
missing)
f f f f
7-91
D
Braking resistor fault (ON: Resistor overheat or braking transistor fault)
f f f f
E
Fault (ON: Faults other than CPF00, CPF01 have occurred.)
f f f f
9-2
F
Not used. (Set when the terminals are not used.)
10
Minor fault (ON: Alarm displayed)
f f f f
9-6
11
Fault reset command active
f f f f
12
Timer function output
f f f f
7-45
13
Frequency agree 2 (Detection width: L4-04)
f f f f
7-90
14
Desired frequency agree 2
[ON(: Output frequency = L4-03, detection width in L4-04) and during frequency agree]
f f f f
7-90
15
Frequency detection 3 (ON: Output frequency L4-03, detection width in L4-04)
f f f f
7-90
16
Frequency detection 4 (ON: Output frequency L4-03, detection width in L4-04)
f f f f
7-90
17
Overtorque detection 1 NC (NC Contact: Torque detection at OFF)
f f f f
7-94
18
Overtorque detection 2 NO (NO Contact: Torque detection at ON)
f f f f
7-94
19
Overtorque detection 2 NC (NC Contact: Torque detection at OFF)
f f f f
7-94
1A
During reverse run (ON: During reverse run)
f f f f
1B
During baseblock 2 (OFF: During baseblock)
f f f f
1C
Motor selection (Second motor under selection)
f f f f
1D
Regenerating (ON: Regenerating)
× × ×
f
1E
Restart enabled (ON: Restart enabled)
f f f f
7-93
1F
Motor overload (OL1) pre-alarm (ON: 90% or more of the detection level)
f f f f
7-78
20
Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting)
f f f f
7-78
30
During torque limit (current limit) (ON: During torque limit)
× ×
f f
31
During speed reference limit. (ON: During speed reference limit)
× × ×
f
33
Zero-servo end (ON: Zero-servo function completed)
× × ×
f
7-78
37
During run 2 (ON: Frequency output, OFF: Base block, DC injection braking, initial excitation, opera-
tion stop.
f f f f
7-78
8