8.2 Programming Mode Constants
8-17
8.2.3 Reference Constants: d
J
Preset Reference: d1
Name
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
d1-01
Frequency reference
1
Sets the frequency reference in the
units used in o1-03 (frequency
reference dis
la
/set units.
The
0.00
f
Q Q Q Q
6-7
Reference 1
.
factory setting unit for o1-03 is
Hz.
.
d1-02
Frequency reference
2
The frequency reference when the
multi-function input “multi-step
speed reference 1” is ON.
0.00
f
Q Q Q Q
6-7
Reference 2
Display units can be set using
o1-03.
.
d1-03
Frequency reference
3
The frequency reference when the
multi-function input “multi-step
speed reference 2” is ON.
0.00
f
Q Q Q Q
6-7
Reference 3
Display units can be set using
o1-03.
.
d1-04
Frequency reference
4
The frequency reference when the
multi-function input “multi-step
speed reference 1, 2” is ON.
0.00
f
Q Q Q Q
6-8
Reference 4
Display units can be set using
o1-03.
.
d1-05
Frequency reference
5
The frequency reference when the
multi-function input “multi-step
speed reference 3” is ON.
0.00
f
B B B B
6-8
Reference 5
Display units can be set using
o1-03.
0to
400.00
.
d1-06
Frequency reference
6
The frequency reference when the
multi-function input “multi-step
speed reference 1, 3” is ON.
0.00
f
B B B B
6-8
Reference 6
Display units can be set using
o1-03.
.
d1-07
Frequency reference
7
The frequency reference when the
multi-function input “multi-step
speed reference 2, 3” is ON.
0.00
f
B B B B
6-8
Reference 7
Display units can be set using
o1-03.
.
d1-08
Frequency reference
8
The frequency reference when the
multi-function input “multi-step
speed reference 1, 2, 3” is ON.
0.00
f
B B B B
6-8
Reference 8
Display units can be set using
o1-03.
.
d1-09
Jog frequency refer-
ence
The frequency reference when the
multi-function inputs, “Jog fre-
quency reference selection,”
“FJOG command,” and “RJOG
6.00
f
Q Q Q Q
6-8
Jog Reference
command” are ON.
Display units can be set using
o1-03.
.
J
Reference Limits: d2
Name
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
d2-01
Frequency reference
upper limit
Sets the output frequency upper
limit as a
ercenta
e of the maxi-
0.0 to
100.0
×
B B B B
7-57
Ref Upper Limit
mum output frequency.
110.0
.
8